Circuit Breaker Size Selector – What Size Breaker for Your Load

Use the free Circuit Breaker Size Selector below: your data never leaves your browser — all work happens on your device, and nothing is uploaded to any server.

What a breaker actually does

A circuit breaker is an automatic switch that opens when current exceeds its rating for long enough to matter. It protects the wire, not the appliance. That distinction is the key to sizing: the breaker must be small enough that the wire never carries a dangerous current for long, yet large enough that the normal load never trips it. A breaker that is too small causes nuisance trips and invites the dangerous workaround of fitting a larger one without upgrading the wire. A breaker that is too large lets the wire overheat before it ever trips.

Standard breaker sizes form a fixed ladder: 15, 20, 25, 30, 40, 50, 60, 70, 80, 90, 100, 125, 150, 175, 200 amps and beyond. You cannot buy a 23-amp breaker, so the job of this selector is to take your load, apply the continuous-load rule, and step up to the next standard size. The continuous-load rule is the part most people miss: a load that runs for three hours or more must be planned at 125 percent of its current, which means the breaker must be at least 125 percent of the continuous load.

The continuous-load rule in practice

A 16-amp heater that runs all evening is a continuous load. At 125 percent it needs a breaker rated at least 20 amps, so the selector suggests 20 amps. The same 16 amps as a short, intermittent load, such as a saw that runs for minutes at a time, needs only a breaker at or above 16 amps, and the next standard size is again 20 amps, so the two cases agree here. The difference shows up at other values: a 24-amp continuous load needs 30 amps of breaker, while a 24-amp intermittent load needs only the next size above 24, which is 25 amps.

A worked example

Consider an electric vehicle charger drawing a continuous 32 amps. The continuous-load rule gives 40 amps required, and the next standard size is exactly 40 amps, so the selector suggests a 40-amp breaker with wire rated for 40 amps. Now consider a charger drawing 40 amps continuously. The rule gives 50 amps, and the selector suggests a 50-amp breaker. That jump surprises owners who expected a 40-amp breaker for a 40-amp charger, but it is the rule working as intended: the breaker must carry the continuous load at only 80 percent of its rating.

A second example shows the intermittent side. A workshop circuit with a 28-amp intermittent load needs a breaker at or above 28 amps, and the selector suggests 30 amps. If that same 28 amps were continuous, the requirement would be 35 amps and the suggestion would be 40 amps. The five-amp difference between the two suggestions is entirely the continuous-load rule, and it is why the selector asks the question explicitly instead of guessing. If you are unsure whether a load counts as continuous, treat it as continuous.

Common mistakes when choosing a breaker

The most dangerous mistake is upsizing a breaker to stop nuisance trips without upsizing the wire. A breaker that trips is telling you something: either the load is too large, the circuit is overloaded, or there is a fault. Replacing a 20-amp breaker with a 30-amp breaker on 12 AWG wire silences the symptom and removes the protection. The second mistake is sizing from the appliance nameplate maximum instead of the actual load, which oversizes the breaker and the wire together and wastes money without adding safety.

Frequently asked questions

Can I use a larger breaker if the wire is larger? Yes, the breaker protects the wire, so a larger wire allows a larger breaker, up to the panel and load limits. The breaker must never exceed the wire rating. Why 125 percent for continuous loads? Because breakers and wires heat up over hours, and the margin keeps the breaker from tripping on a long run and keeps the wire within its temperature rating. What if my load needs more than 400 amps? That is beyond this selector and beyond ordinary residential work. It needs a professional design with switchgear, not a bigger off-the-shelf breaker.

Safety first: an estimate, not a code approval

Every electrical tool on this page is an educational estimator only. It is never professional advice and never a substitute for a licensed electrician. Electrical codes differ by country, region and building type, and they change over time. A result that looks fine here can still fail a local inspection, and a result that looks tight here can still be acceptable under a rule this simple calculator does not model, such as temperature correction, grouping, or a special location rule. Before you buy cable, cut a wall, or touch a panel, check your local electrical code and talk to a licensed electrician. Breaker, conduit and box-fill results are estimates, not code-compliance guarantees. If you are unsure about any part of a job, stop and ask a professional. Electricity can injure or kill, and no free online calculator changes that fact.